NOTE 3: For RCD Type B, tripping is achieved for residual pulsating direct currents superimposed on a smooth direct current up to 0.4 times the rated residual current (IΔn) or 10 mA, whichever is the highest value. In some other countries in Europe (perhaps not coincidentally the ones commonly using 3-phase supply to homes), it's much easier to find type-A or even type-B. Where electric vehicle charging equipment is likely to create a residual DC fault current, manufacturers may provide the correct type of RCD within the charging equipment. However, problems could arise if the charging equipment is installed downstream of an existing Type AC RCD, which could be blinded by the residual DC fault current. In some types of DC charging equipment, the AC input side is galvanically isolated from the DC output which, hence, provides electrical separation. This means that faults on the DC output side, connected to the vehicle, would not be detected by an RCD on the input side of the circuit. What are the hazards and problems? An RCD monitors the earth leakage current in a circuit. It is constructed from coils of wire wound around a ferrite toroid core, one for each live conductor of the circuit protected. When a current imbalance between live conductors is detected, a voltage will be induced in the tripping coil which will disconnect the electrical supply to the protected circuit (see Figure 1). i) RCD Type AC: RCD tripping on alternating sinusoidal residual current, suddenly applied or smoothly

Many studies on the in-service reliability have been carried out on RCDs installed in a wide range of installations providing an insight into the effects that environmental conditions and external factors can have on the operation of an RCD. Key information: It is important to understand that RCDs cannot limit voltage or current, they provide protection by limiting the time a specific maximum current can flow to earth. The initial verification required under 641.1 and 301.1 (ii), covers the requirements for the verification that electrical equipment (any appliance supplied or connected, as part of the existing fixtures and fittings) is compatible with other electrical equipment such as RCDs installed to provide additional protection e.g. for a domestic installation, document the appliance RCD requirements with the justification for the consumer unit specification. RCD failing to trip when the appliance is running, and the RCD test button is operated, could be an indication that the appliance is affecting the RCD. The RCD type should not be confused with the different types of circuit-breakers which are manufactured according to their time/current characteristics. Circuit-breakers for overcurrent protection of cables are available in types B, C and D in accordance with BSEN 60898-1. It's quite easy to see how an RCBO with a B Type time-current curve could be mistaken for a Type B RCD.Type B devices are also suitable for Type AC, Type A and Type F applications. How do I test the different Types of RCD? Some European countries have already banned the general use of Type AC RCDs and some manufacturers have stopped making them, supplying Type A in place of Type AC. ii) RCD Type A: RCD tripping on alternating sinusoidal residual current and on residual pulsating direct current, suddenly applied or smoothly increasing. Type AC RCDs are in clause 531.3.3 of BS7671 2018, because they are still in EN 60364-5-53 2015. The UK have just adopted this line from the EN standard. It should be noted that the residual DC leakage current can vary with motor speed and cable length.

There's never going to be a perfect solution but there does need to be a less complex solution than there is. NOTE 4: For guidance on the correct use of RCDs for household and similar use, see PD IEC/TR 62350. Commercial installations comprising LED lighting and large quantities of IT equipment which can also cause other issues, such as protective conductor current which should also be considered.

Type AC RCDs subjected to pulsed waveforms will not trip within the safe limits, required for 30mA protection. Appliances containing diodes, produce pulsed residual currents – see Fig 1. Diodes became so common in domestic equipment some years ago, that many countries banned the "general use" of Type AC RCDs e.g. From 1985, VOE Regulations specified the use of Type A RCDs in all domestic installations as a minimum requirement. In the 18 th Edition, the term for discrimination has been changed to selectivity. It is important to achieve selectivity when installing multiple RCDs in series. A common misconception is that an RCD with a higher mA sensitivity rating will provide selectivity, but this is not the case due to the instantaneous operation of the device. The only way to achieve selectivity with RCDs is to install a time-delayed device upstream. I believe the article makes it clear that the their are 4 Types of RCD that may need to be considered - Quote from the article -

Modern appliances are becoming increasingly more sophisticated, featuring microprocessor technology with an emphasis on energy reduction. This has led manufacturers to incorporate energy-saving measures, such as speed control, which by the nature of its operation has an element of DC residual fault current. Which types of installation could be affected? RCDs are far more sensitive than circuit-breakers. The sensitivity being rated in milliamps (mA) as opposed to amps (A). Different Types of RCD If equipment contains Power Electronic Converter Systems (PECS), more commonly known as inverters or VSDs, BS 62477-1 Safety requirements for power electronic converter systems and equipment sets out the requirements and Annex H provides guidelines for RCD compatibility. Manufacturers must define the safety requirements clearly for suitable RCDs. If this information cannot be obtained, a Type B RCD should be installed to cover the worst-case scenario. i.e. WWFC 1877 Mr Wolves Football supporter I guess - This article raises several questions commonly posed by Installers (see the question marks). High frequency current components can saturate the RCD, preventing detection of 50Hz residual currents.Residual Current Circuit-Breaker (RCCB) without protection against overload BS EN 61008, BS 4293, BS EN 62423. UK electricians can still make informed technical decisions. This is explained in Chapter 12, 13 and Chapter 30. The Electrician is responsible, not the Technical committee, to make the decision on which device is appropriate for the installation. The revised RCD guidance in 531.3.3 is precise. The appropriate Type of RCD must be selected, based on the characteristics of the residual current and the equipment that is likely to be connected to the RCD protected circuit. and the RCD should be selected based on the characteristics of the connected loads.

For existing installations, problems associated with the following may indicate that Type F is required in place of Type A: Type A RCDs are not designed to detect smooth dc residual currents. They will still trip within safe limits with < 6 mA smooth dc superimposed on a 50Hz pulsed residual current. Type A RCDs are used for alternating sinusoidal residual current and for residual pulsating direct current up to 6 mA. There are many different RCD types available, each being suitable for different equipment types, as identified in Regulation 531.3.3 of BS 7671:2018.A well-timed subject. Just a few weeks ago I tried to find a new RCD to replace an old BS4293 one. I have seen how a pure type-AC RCDs rated for 30 mA trip can allow multiple amps of half-wave-rectified current without tripping. As this is a TT installation where earth fault protection depends on the RCD, it feels very inappropriate to have anything less than a type-A, given that plenty of loads contain rectifiers. (Admittedly, the old one was presumably only like type-AC, but that's not an excuse.) Residual Current Device is a generic term used for describing devices which incorporate residual current protection in accordance with one of the standards below: The fault current (If) contains mixed frequency components between 10Hz (minimum motor frequency) and 1kHz (maximum inverter switching frequency) ***.